Measured values
|
temperature
|
Output voltage
|
TRV: 1x 0..10 V or 0..5 V
|
Output current
|
TRA: 1x 4..20 mA
|
Output passive
|
PT100 | PT100 1/3 DIN | PT1000 | PT1000 1/3 DIN | Ni1000 | Ni1000TK5000, NTC10k | NTC 10k Precon | NTC5k | NTC20k | NTC1,8k, LM235Z, KTY81-110 | KTY81-121 | KTY81-122 | KTY81-210
|
Power supply
|
15..24 V = (±10%) or 24 V ~ (±10%) SELV, TRA: 15..24 V = (±10%) SELV
|
Power consumption
|
TRV: typ. 0,4 W (24 V =) | 0,8 VA (24 V ~), TRA: max. 0,5 W (24 V =)
|
Measuring range temp.
|
passive:, depending on used sensor
|
Output signal range temp.
|
TRV | TRA:, Scaling analog output, -50..+50 °C (default setting), selectable from 8 temperature ranges -50..+50 | -20..+80 | -15..+35 | -10..+120 | 0..+50 | 0..+100 | 0..+160 | 0..+250 °C, adjustable at the transducer
|
Operating temperature range
|
permissible working temperature, enclosure active: -35..+70 °C, enclosure passive: -35..+90 °C
|
Accuracy temperature
|
passive: depending on used sensor, PT100 | PT1000: ±0,3 K (typ. at 0 °C, Kl.B), Ni1000: ±0,4 K (typ. at 0 °C), Ni1000TK5000: ±0,4 K (typ. at 0 °C), NTC10K: ±0,22 K (typ. at 25 °C), ±0,5 K (typ. at 21 °C within default measuring range)
|
Sensor
|
passive: 2-wire (standard), 3-wire or 4-wire
|
Enclosure
|
enclosure USE-S, PC, pure white
|
Protection (IP)
|
IP65 according to EN 60529, SI-Protection (not possible for electronic Sensors)
|
Cable entry
|
Flextherm M20 for wire Ø=4,5..9 mm, removable
|
Electrical connection
|
removable plug-in terminal, max. 2,5 mm²
|
Pocket
|
stainless steel V2A, Ø=6 mm, L=25 mm
|
Ambient condition
|
max. 85% rH short term condensation
|